Per-circuit consumption step-change.
A sub-metered circuit's consumption or run-fraction steps change with no merchandising or load change.
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
energy
high
optimized tier
AI: hybrid
- Related metric
per_circuit_load
- Trigger
circuit_kwh or run_fraction step-change vs baseline
- Value drivers
-
Avoided truck rolls
Asset lifespan
Energy savings
- Preconditions
- Per-circuit submetering on the load.
- Human role
- Scopes the equipment check and the visit.
- Action plan
-
(1) Attribute the change to the exact circuit (RTU, refrigeration rack, lighting panel).
(2) For refrigeration/RTU: check door seals/gaskets, condenser-coil fouling, refrigerant charge before product loss.
(3) Convert an emergency truck roll into a scheduled visit with the right scope.
- Escalation
-
(1) Step-change with a rising-current signature → degradation; book service before failure.
(2) Circuit drawing during scheduled off-hours → schedule/contactor fault.
- Prevention
-
(1) Per-circuit baselines refreshed after equipment or merchandising changes.