Loss of communication with the panel.
Keedian loses its read connection to the fire-alarm panel — the panel's heartbeat is no longer received. The system's state can no longer be seen, so a supervisory or trouble condition arising during the outage would go unnoticed. For a life-safety system this is escalated, not assumed normal.
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
fire_safety
urgent
essential tier
AI: hybrid
- Related metric
fire_system_readiness
- Trigger
panel_heartbeat lost for > comms_timeout (raises unmonitored escalation)
- Value drivers
-
Operational continuity
- Preconditions
- A panel heartbeat / poll over the monitoring interface with a configurable comms_timeout, so a brief network blip is distinguished from a sustained loss of the feed.
- Human role
- Primary — Keedian detects the loss of the panel feed and escalates; restoring the panel interface is coordinated with the customer and the licensed provider. Operators confirm the loss is the integration and not a wider fault and drive it to restoration.
- Action plan
-
(1) Confirm the loss is sustained past comms_timeout, not a transient network blip.
(2) Escalate — a fire system Keedian cannot read is a compliance and safety gap; report the panel state as unknown rather than assumed normal.
(3) Coordinate restoration of the interface with the customer and the licensed provider; keep the outage window on record.
- Escalation
-
(1) Loss sustained beyond the agreed window → escalate to the customer immediately; do not hold for the routine report.
(2) Recurrent loss on the same panel → flag the integration path (gateway, relay board, network) for a permanent fix.
- Prevention
-
(1) Confirm the heartbeat / poll and comms_timeout per panel at onboarding.
(2) Monitor the integration path health so a degrading link surfaces before it drops entirely.