Keedian operations · Standard procedure
High DeltaT.
DeltaT above the ceiling during active cooling — airflow-side (clogged filter, blower failure, closed dampers, ducting obstruction).
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
hvac
medium
essential tier
AI: hybrid
- Related metric
cooling_delta_t
- Trigger
(RAT − SAT) > threshold_max during cooling_mode (sustained)
- Value drivers
-
Energy savings
Customer experience
- Preconditions
- RAT and SAT sensors operational; cooling mode detectable.
- Human role
- Primary — dispatch decision.
- Action plan
-
(1) Sensor sanity check.
(2) If a filter ΔP sensor is present (Optimized add-on), confirm filter restriction.
(3) Dispatch with airflow scope (filter → blower → dampers).
- Escalation
-
(1) Filter ΔP sensor not present and recurrence > 1 event in 14 days → dispatch with airflow scope (filter, blower, dampers).
(2) Blower fault confirmed remotely → dispatch within 48h; comfort risk grows as building load increases through the day.
(3) Recurrent dampers / ducting issue → flag for capital review (not a maintenance issue).
(4) High DeltaT co-occurs with a Temperature Compliance failure → out-of-cycle notification to client; comfort impact is in progress.
- Prevention
-
(1) Filter-replacement cadence calibrated to site dust load — high-dust sites (urban, food-service kitchen exhaust) need shorter intervals than the manufacturer default.
(2) Damper-position audit at install and at quarterly cadence — closed or stuck dampers are a recurring source of high ΔT that visual inspection catches early.
(3) Blower performance baseline captured at install — gives the operator a reference to compare against when remote signals first deviate.