Procedure
Step 1 — Access SC/SC+
- Log into SC/SC+ with your credentials and open the main dashboard.
Step 2 — Review Active Alarms
- From the main page, review any active alarms displayed for the site.
Step 3 — Navigate to Spaces Page (If Applicable)
- For RTUs, chillers, and boilers, open the Spaces page from the main dashboard to locate the affected equipment.
Step 4 — Select Affected Unit
- Identify and select the specific unit associated with the alarm to open its detailed view.
Step 5 — Attempt Alarm Reset
- Open the Settings tab inside the unit detail view and attempt to reset the alarm.
Step 6 — Escalation (If Required)
- If the alarm does not reset or remains active, follow the SOP for Dispatching a Corrigo Work Order.
Troubleshooting
Alarm does not reset.
Solution. Confirm correct unit selection and attempt the reset again. If still unsuccessful, dispatch a Corrigo Work Order.
Unit not visible on the Spaces page.
Solution. Verify the correct site is selected, refresh SC/SC+, or sign out and back in to restore system data.
No alarms visible on the main page.
Solution. Confirm filters are not limiting alarm visibility; ensure the correct site and system view are selected.