Off-hours consumption above floor.
Closed/unoccupied-hours consumption sits above the store's expected overnight floor — energy burned while the site should be idle.
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
energy
medium
essential tier
AI: hybrid
- Related metric
energy_consumption
- Trigger
off_hours_kwh > expected_overnight_floor (sustained)
- Value drivers
-
Energy savings
Sustainability
- Preconditions
- Defined operating hours per site; main-meter interval data.
- Human role
- Reviews the anomaly and works the end-of-day checklist with the site.
- Action plan
-
(1) Confirm the off-hours floor against the site's own overnight minimum — flag, do not auto-attribute (no weather/occupancy normalization in V1).
(2) Walk the end-of-day checklist with the site: lighting/signage timeclock or contactor, HVAC night setback, no refrigeration case in continuous run.
(3) Where sub-metered, attribute the residual draw to the exact circuit and point the site at it.
(4) Energy Intelligence reads the meter — we guide the fix; we do not switch loads remotely.
- Escalation
-
(1) Floor creeps week over week → refrigeration service check (charge / fouled condenser) or a stuck contactor.
(2) Persists 2+ months with no fix → flag for the client at the monthly review (timeclock / controls retrofit candidate).
- Prevention
-
(1) Timeclock / smart-thermostat scheduling on lighting and HVAC so the floor drops at close.
(2) Monthly baseload-ratio watch per site to catch "never turns off" buildings early.