Sustained temperature out-of-range.
Space temperature has been outside the expected band for longer than the noise / startup tolerance window — a real condition, not a transient.
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
hvac
high
optimized tier
AI: hybrid
- Related metric
temp_compliance
- Trigger
space_temp outside target_band for duration > dwell_threshold
- Value drivers
-
Customer experience
Avoided truck rolls
- Preconditions
- Expected band + dwell window + continuous data stream.
- Human role
- Primary — dispatch decision.
- Action plan
-
(1) Validate data continuity (any gap in the stream?).
(2) Cross-check Runtime and Cooling DeltaT to localize the issue (capacity, control, or load mismatch).
(3) Attempt remote remediation (setpoint or schedule adjustment).
(4) Dispatch if remote action does not resolve.
- Escalation
-
(1) Dwell exceeds 4 hours during business hours → dispatch within SLA; comfort impact is likely.
(2) Data gap suspected → escalate internally to the technical team; do not report the site as a real failure until the gap is resolved.
(3) Same site recurrent > 3 events in 30 days → schedule a capacity assessment; the comfort-failure pattern may indicate undersized equipment.
(4) Out-of-range correlated with a known schedule or setpoint change → roll back the change and reclassify as an operator-induced event.
- Prevention
-
(1) Data-continuity monitoring at platform layer — gap detection at minute-level cadence prevents the gap from being misclassified as a comfort failure.
(2) Dwell-window calibration per zone — too-short dwell windows fire on transient events that aren't real comfort issues; too-long windows hide real failures.
(3) Site-change watchlist — any site with a recent remodel, equipment swap, or capacity change gets tighter monitoring for the following 30 days to catch undersizing early.