Sustained undervoltage.

Service voltage sits below the lower band for several intervals — chronic undervoltage overheats motors and shortens their life.

01 Detail

Trigger, action plan, and escalation criteria.

optimization_metric energy high optimized tier AI: hybrid
Related metric
service_voltage
Trigger
rms_voltage < lower_band for 3+ consecutive intervals
Value drivers
Asset lifespan Avoided truck rolls
Preconditions
Voltage telemetry at the service; nominal band on file.
Human role
Files the utility / power-quality claim and pre-empts equipment damage.
Action plan
(1) Confirm RMS voltage below the lower band (ANSI C84.1 Range B ~ -8.3% / EN 50160 -10%) for 3+ consecutive intervals. (2) Notify the utility — the service / transformer / neutral is their responsibility; log a power-quality claim. (3) Expect elevated motor current → schedule a compressor check before burnout.
Escalation
(1) Voltage event correlated with an equipment trip → attribute to power quality vs internal fault to avoid a wasted diagnostic truck roll. (2) Recurring undervoltage → push the utility on the service.
Prevention
(1) Track voltage band-compliance per site; raise chronic issues with the utility proactively.