(1) Acknowledge the alarm; confirm store number and source; begin investigation without delay (HIP alarms are Critical, never suppressed).
(2) Review BAS data: current indoor temp, trend, cooling stage, equipment status, fan operation, alarm duration; classify as temporary spike, equipment failure, or sensor error.
(3) Attempt remote corrective actions if BAS controls allow: lower cooling setpoint, enable cooling stage, verify fan, reset HVAC unit, confirm sensor accuracy.
(4) If temperature stabilizes, continue monitoring, document actions, and close the alarm event.
(5) If temperature remains elevated for ~15 minutes, create a CMMS dispatch ticket with store number, equipment ID, current temperature, and "HVAC HIP alarm – Temperature Illness Prevention event."