Recurring door fault.
A unit logs repeated door faults — nudging, reopening, or door-time-out events — inside a rolling window without a full stoppage yet. A degradation signal: the door operator is the most common cause of an eventual out-of-service, so it is referred before it strands the car.
01 Detail
Trigger, action plan, and escalation criteria.
optimization_metric
vertical_transport
low
essential tier
AI: hybrid
- Related metric
vertical_transport_availability
- Trigger
count(door_fault, window) >= door_fault_threshold (raises recurring-door-fault degradation)
- Value drivers
-
Avoided truck rolls
Operational continuity
- Preconditions
- Door-fault events are exposed from the controller and counted per unit over a configurable rolling window and count threshold, both server-side attributes confirmed per building.
- Human role
- Primary — Keedian counts the recurring faults and raises the degradation alarm; the door-operator service is the certified maintenance provider's. Operators confirm the trend and coordinate a planned referral rather than an emergency one.
- Action plan
-
(1) Count door-fault events per unit over the rolling window; raise the alarm when the count crosses the agreed threshold.
(2) Refer it to the maintenance provider as a planned door-operator check — a degradation signal, not an emergency — with the fault count and window.
(3) Log the referral and keep watching; if the unit stops fully, it escalates to the out-of-service alarm.
- Escalation
-
(1) Door-fault rate accelerating sharply → move the referral forward before the expected stoppage.
(2) Faults continue after a provider visit → flag the door operator for a deeper engagement.
- Prevention
-
(1) Set the window and count threshold per building so a normal fault rate is not over-reported.
(2) Trend door-fault counts per unit so chronic doors are worked on a planned basis.