Whether the rack holds discharge (high-side) pressure under control against its commissioned limits, and whether its protection sequence behaves. Sustained high discharge pressure, an approach to the trip threshold, a discharge trip, or repeated auto-resets each put the whole rack — and every case it feeds — at risk at once. The high-discharge setpoint, delay, and trip fields are controller / commissioning parameters, not separate metrics.
The table below summarizes the alarms that fire directly from Rack Discharge Pressure. Each row links to the full operational detail (trigger, preconditions, action plan, human role, escalation, prevention) in the SOPs catalog.
| Alarm | Description | Severity | Tier | AI executes? | Value drivers | SOP |
|---|---|---|---|---|---|---|
| High discharge pressure sustained | The rack holds discharge (high-side) pressure above its commissioned high-discharge setpoint for longer than its delay. Sustained high-side pressure loses capacity across every case the rack feeds and, unaddressed, walks toward a protection trip. | High | Managed | Hybrid | Operational continuity · Product loss prevention · Asset lifespan | Open SOP → |
| Discharge trip approach | Rack discharge pressure is approaching the configured trip threshold — the rack is close to a protective shutdown that would take every case it feeds offline at once. A lead-time warning to act before the trip. | High | Managed | Hybrid | Operational continuity · Product loss prevention · Asset lifespan | Open SOP → |
| Discharge protection trip | The rack's discharge protection has tripped after its configured trip setpoint and delay — a protective shutdown that takes the whole rack offline and puts every case it feeds at risk simultaneously. The highest-urgency rack event. | High | Managed | Hybrid | Operational continuity · Product loss prevention · Asset lifespan | Open SOP → |
| Repeated discharge resets | The rack's discharge protection auto-resets repeatedly, or trips recur after the configured auto-reset — a rack running on the edge of its protection band that masks a developing fault behind automatic recovery. | High | Managed | Hybrid | Operational continuity · Asset lifespan · Energy savings | Open SOP → |
The action plan for each alarm lives on its own SOP page in the SOPs catalog — with the diagnostic steps, human role, value drivers, escalation, and prevention specific to that alarm. The list below maps each alarm to its SOP.